Surge Protection with Acti9 iQuick PRD40r
Designed to ensure optimal protection in residential installations and in structures of significant size, the Acti9 iQuick PRD40r arrester effectively defends against the risks of direct and indirect transient overvoltages.
Type 2 Self-Protected Device
With a high risk level identified for the input panel board, the PRD40r has the advantage of being a self-protected Type 2 device. It also includes remote reporting with a “Cartridge needs to be changed” message should the need arise.
Quick replacement of pre-wired cartridges
One of the salient features of the Acti9 iQuick PRD40r unloader is the ability to quickly change the removable cartridges in case of damage, thanks to its pre-wired structure.
Acti9 iQuick PRD40r Technical Specifications
- Compatibility with TT and TN-S earthing system
- Breaking capacity Isc: 20 kA
- Maximum discharge current Imax: 40 kA
- Nominal discharge current In: 20 kA
- Maximum operating voltage in differential mode: 350 V AC
- Maximum common mode operating voltage: 264V AC between neutral and earth, 350V AC between phase and earth
Up Voltage Protection Parameters
The level of protection of the Up voltage varies according to the modes, with a maximum of 2.5kV in differential mode and 1.5kV in common mode. The device operates at a nominal operating voltage Un of 230V AC or 400V AC, with a frequency of 50 Hz or 60 Hz.
Dimensions and Environmental Specifications
- Dimensions: (W) 131.5mm x (H) 103.8mm x (D) 75.9mm
- Weight: 850 g
- Degree of protection: IP20 and IP40 in a modular housing
- Operating temperature: -25°C and +60°C
- Storage temperature: -40°C and +85°C
Regulatory Compliance
The product complies with IEC/EN 60947-5-1, EN 61643-11:2012 type 2 and IEC 61643-11:2011 standards, thus ensuring its reliability and safety.